DC voltage transmitter: converts DC voltage input in the range of 0 to 1000V into an industrial standard signal output. The product is powered by a 20-30V DC power supply, with isolation among input, output, and power supply.
Model | CZDL-VDC-M |
Input | |
Input voltage range(Un) | 0~1000V DC |
Max . input voltage(Umax) | 1.2×Un ( Long term );2×Un ( ≥1 Min ) |
Voltage input impedance | ≥100kΩ ( 9,10 ) |
≥400kΩ ( 8,10 ) | |
≥1.6MΩ ( 7,10 ) | |
Remark | The customer needs to specify the input voltage range when placing an order. |
Output | |
Current output | 0~20mA/4~20mA |
Max . output current | ≤22mA |
Load resistance | ≤300Ω |
Voltage output | 0~10V/0~5V/1~5V |
Max . output voltage | ≤11V ( 0~10V Output range ) |
≤6V ( 0~5V/1~5V Output range ) | |
Load resistance | ≥10kΩ |
Remark | The customer needs to specify the output voltage or output current when placing an order. |
Parameter | |
Supply voltage | 20V~30V DC |
Rated power consumption | Current Output≤55mA ( Powered by 24V DC,20mA Output ) |
Voltage Output≤35mA ( Powered by 24V DC,10V Output ) | |
Transfer accuracy | 0.1%F.S |
Temperature drift | 0.01%F.S./℃ |
Response time | 200ms reach 90% of final value |
Operating temperature | -20℃~+60℃ |
Storage temperature | -40℃~+80℃ |
Relative humidity | 10%~90% |
Pollution degree | 3 |
EMC | GB/T 18268 |
Safety parameters | |
Insulation performance test standards | GB4793.1 |
Dielectric strength (input-output, power) | 2500V AC,50Hz,1min |
Dielectric strength (power-output) | 1500V AC,50Hz,1min |
Insulation resistance | ≥100MΩ |
IP degree (Comply with IEC60529) | IP20 |